The T-VER-E50B2 Power & Energy Meter supports monitoring of single-phase as well as split- and three-phase circuits that have a neutral available and also circuits that do not include a neutral. These are designated in the E50B2 setup as 2L (no neutral) or 2L+1N (with a neutral), and for three-phase applications, 3L and 3L+1N respectively. The way derived channels are calculated is affected by whether or not a neutral is selected in the configuration.

Please keep in mind that the E50B2 output pulses are based on Amp/hours, Watt/hours, and VAR/hours, which are logged by the HOBO data logger. If the HOBO UX120-017 is logging these pulses, HOBOware will use the pulse values to calculate VAR, VA, Volts, Amps (either phase-to-phase or phase-to-neutral), Power, and PF. If you are using a logger other than the UX120-017, these calculations must be done in Excel using the spreadsheet found here under Documentation.

Attached is a screenshot of two data plots from HOBOware. These were recorded with the E50B2 connected to the same circuit - a 240VAC split-phase US home service. One data set was recorded with the E50B2 set for 2L (no neutral) the other was 2L+1N (with neutral). You can see how the calculated voltage and current are affected by the change in configuration. Also note that resultant power and energy are unaffected.

Image

Categories

Tech Note
Getting Started
Software