Differential Air Pressure Transducer Sensor

Part # T-VER-PXU-L
 
 
$220


Overview

The T-VER-PXU-L is a differential air pressure transducer that utilizes a highly accurate and stable sensor, which is microprocessor profiled for improved accuracy and reliability. The stability, accuracy, and ease-of-use characteristics of the PX models make them the ideal product for differential pressure monitoring applications.

Requires analog input option during RX3000 or U30 system configuration and use of a S-FS-CVIA when using the H22-001 data logger. When using a U12 data logger, this sensor requires an 0-5 Vdc analog input cable (CABLE-ADAP5) and external power provided by an AC adapter (AC-SENS-1).

Highlighted Features

  • User selectable units, uni- or bi-directional pressure ranges and analog output (mA or Vdc)
  • LCD display
  • Panel or duct mounting (probe included)
  • High accuracy

In what environment does this sensor operate?

This sensor operates in an indoor environment.

What measurements does this sensor support?

The T-VER-PXU-L sensor supports the following measurement: Differential Pressure

The T-VER-PXU-L is a differential air pressure transducer that utilizes a highly accurate and stable sensor, which is microprocessor profiled for improved accuracy and reliability. The stability, accuracy, and ease-of-use characteristics of the PX models make them the ideal product for differential pressure monitoring applications.

Requires analog input option during RX3000 or U30 system configuration and use of a S-FS-CVIA when using the H22-001 data logger. When using a U12 data logger, this sensor requires an 0-5 Vdc analog input cable (CABLE-ADAP5) and external power provided by an AC adapter (AC-SENS-1).

Highlighted Features

  • User selectable units, uni- or bi-directional pressure ranges and analog output (mA or Vdc)
  • LCD display
  • Panel or duct mounting (probe included)
  • High accuracy

In what environment does this sensor operate?

This sensor operates in an indoor environment.

What measurements does this sensor support?

The T-VER-PXU-L sensor supports the following measurement: Differential Pressure

To see the full specifications for this product, please see our product manual found under the documentation tab if available.

Measurement ranges:  selectable uni- or bidirectional 0.1, 0.25, 0.5, 1.0, 2.5,5,10 "W.C.; (selectable also in Pascal units)  
Accuracy:  +/- 1% full scale of selected range
Sensor supply:  12 - 30VDC or 24 VAC., 35 mA 
Medium:  dry air, inert gas
Operating temperature range:  0 to 600C (32 to 1400F)
Humidity range:  10 - 90% non-condensing
Response time:  (selectable) Fast, 2 sec; Standard, 20 sec
Output:  (selectable) 4 - 20mA or 0 -5VDC or 0 - 10VDC 
Dimensions:  4.5x3.3x2.2 in (114x84x55 mm) - probe length 8.75 in. (22.23 cm)
Weight:  7.2 oz
Display (L model only):  signed 31/2 digit LCD
Case:  UL 94 V-O fire retardent ABS
Proof pressure:  3 psid (20.6kPa)
Burst pressure:  5 psid (34.5kPa)
CE