Product Image Viewer
˂
  • T-VER-PXU-L
˃

Differential Air Pressure Transducer Sensor

Part # T-VER-PXU-L
 
 

Overview

The T-VER-PXU-L is a differential air pressure transducer that utilizes a highly accurate and stable sensor, which is microprocessor profiled for improved accuracy and reliability. The stability, accuracy, and ease-of-use characteristics of the PX models make them the ideal product for differential pressure monitoring applications.

Requires analog input option during RX3000 or U30 system configuration and use of a S-FS-CVIA when using the H22-001 data logger. When using a U12 data logger, this sensor requires an 0-5 Vdc analog input cable (CABLE-ADAP5) and external power provided by an AC adapter (AC-SENS-1).

Highlighted Features

  • User selectable units, uni- or bi-directional pressure ranges and analog output (mA or Vdc)
  • LCD display
  • Panel or duct mounting (probe included)
  • High accuracy

In what environment does this sensor operate?

This sensor operates in an indoor environment.

What measurements does this sensor support?

The T-VER-PXU-L sensor supports the following measurement: Differential Pressure

The T-VER-PXU-L is a differential air pressure transducer that utilizes a highly accurate and stable sensor, which is microprocessor profiled for improved accuracy and reliability. The stability, accuracy, and ease-of-use characteristics of the PX models make them the ideal product for differential pressure monitoring applications.

Requires analog input option during RX3000 or U30 system configuration and use of a S-FS-CVIA when using the H22-001 data logger. When using a U12 data logger, this sensor requires an 0-5 Vdc analog input cable (CABLE-ADAP5) and external power provided by an AC adapter (AC-SENS-1).

Highlighted Features

  • User selectable units, uni- or bi-directional pressure ranges and analog output (mA or Vdc)
  • LCD display
  • Panel or duct mounting (probe included)
  • High accuracy

In what environment does this sensor operate?

This sensor operates in an indoor environment.

What measurements does this sensor support?

The T-VER-PXU-L sensor supports the following measurement: Differential Pressure

To see the full specifications for this product, please see our product manual found under the documentation tab if available.

Measurement ranges:  selectable uni- or bidirectional 0.1, 0.25, 0.5, 1.0, 2.5,5,10 "W.C.; (selectable also in Pascal units)  
Accuracy:  +/- 1% full scale of selected range
Sensor supply:  12 - 30VDC or 24 VAC., 35 mA 
Medium:  dry air, inert gas
Operating temperature range:  0 to 600C (32 to 1400F)
Humidity range:  10 - 90% non-condensing
Response time:  (selectable) Fast, 2 sec; Standard, 20 sec
Output:  (selectable) 4 - 20mA or 0 -5VDC or 0 - 10VDC 
Dimensions:  4.5x3.3x2.2 in (114x84x55 mm) - probe length 8.75 in. (22.23 cm)
Weight:  7.2 oz
Display (L model only):  signed 31/2 digit LCD
Case:  UL 94 V-O fire retardent ABS
Proof pressure:  3 psid (20.6kPa)
Burst pressure:  5 psid (34.5kPa)
CE

The following are associated resources for this product. In general users of this product can gain insight into its possible use by utilizing the resources below. Our user forum can also be a valuable resource for questions, use cases and general feedback. Share with us today, here!

Customers Also Bought

CASE-PELICAN-1510

The largest, most durable airline-legal carry-on available, the new 1510 Pelican case provides safe and convenient transport of your HOBO data logging equipment. This watertight, crush-proof, and dust-proof case features a sturdy but lightweight design that includes a Pick N Pluck™ foam interior, 17” retracting extension handle, strong polyurethane wheels, stainless steel hardware, padlock protectors, and a lifetime guarantee of excellence.

Add to Cart
Add to Quote
Compare Product

Compare

Recently Viewed