50 AMP Mini Split-core AC Current Transformer Sensor

Part # T-MAG-0400-50
 
0.4 (10.15mm) Opening
 
$35


Overview

The small size 50 AMP split-core AC Current Transformer (CT) is mounted around a current carrying wire to measure AC amperage. This CT provides a 0 to .333 Volt AC output proportional to current flow and is used with Onset data loggers via the FlexSmart TRMS module and with kWh transducers (WattNodes) for True RMS measurement of sinusoidal and non-sinusoidal waveforms. The result is an accurate current measurement for many types of electrical equipment.

Highlighted Features

  • Rated input from 5 to 50 AMP
  • Output 0.333 Volt AC at rated current
  • Linearity accuracy ± 1%
  • Accuracy at 10% to 130% of rated current
  • Split-core design for fast, easy installation
  • 8 ft. (2.44m) 24 AWG twisted pair leads
  • 0.40" (10.15mm) Opening

In what environment does this sensor operate?

This sensor operates in an indoor environment.

What measurements does this sensor support?

The T-MAG-0400-50 sensor supports the following measurement: AC Current

The country of origin for this product is the United States. To see the full specifications for this product, please see our product manual found under the documentation tab if available.

  • Rated input from 5 to 50 AMP
  • Output 0.333 Volt AC at rated current
  • Operates from 50 Hz to 400 Hz
  • UL Recognized, CE and RoHS compliant
  • Linearity accuracy ± 1%
  • 8 ft. twisted-pair lead
  • Accuracy at 10% to 130% of rated current
  • Self-locking mechanism guaranteed for 500 closing
Compatible Sensors
AC Current
FlexSmart TRMS Module (2 channels)
$95
FlexSmart TRMS Module (2 channels) w/modular plug
$105
Kilowatt Hours
WattNode 208/240 VAC 3-phase Delta/Wye kWh Transducer
$269
WattNode 480 VAC 3-phase Delta/Wye kWh Transducer
$269
WattNode 208/240 VAC 1,2, or 3 Phase Wye kWh Transducer
$229
WattNode 208-240VAC 2 or 3 Branch Circuit kWh Transducer
$249
Accessories
Carrying Case
Pelican Case
$245
Additional Compatible Products
USB Data Loggers - requires external sensor
Micro Station
$231
H22 Energy
$364
U30 USB Weather Station
 
State
$92
Extended Memory State
$121
Kits
kWh Monitoring Kit – UX90 with WattNode Sensors
 
HOBO U30-NRC Weather Station Starter Kit
$1459
Web-based Monitoring Systems - via remote communication
RX3000 Remote Monitoring Station
 
Sensors
E50B2 Power & Energy Meter
$599
WattNode 208/240 VAC 3-phase Delta/Wye kWh Transducer
$269
WattNode 480 VAC 3-phase Delta/Wye kWh Transducer
$269
WattNode 208/240 VAC 1,2, or 3 Phase Wye kWh Transducer
$229
USB Data Loggers - optional external sensors
4-Channel Pulse
$215
4-Channel Pulse
$325
Wireless Data Nodes - via receiver/USB
Four-Channel Data Node
$329
Four External Channel Data Node
$241
Documentation for the T-MAG-0400-50

 
Magnelab Mini AC Current Transformer (T-MAG-0400) Connection Instructions


The following are associated resources for this product. In general users of this product can gain insight into its possible use by utilizing the resources below.

On-demand Webinars & Videos