F300 series sensors are versatile, rugged, high-performance air velocity and air temperature sensors. Designed with conformal coated electronics and sealed enclosures, F300 sensors are suitable for demanding applications, including those in corrosive or alkaline environments. With a robust, splash-proof design and UV-tolerant construction, F300s are built to handle a wide range of product and process-control air flow applications.

Requirements for use with specific data loggers:

  • HOBO MX1100 series: a 0-5 Volt DC input cable (SD-VOLT-05) and external power provided by an AC adapter (AC-SENS-1)
  • HOBO U12, UX120-006M, or ZW series: a 0-5 Volt DC input cable (CABLE-ADAP5) and external power provided by an AC adapter (AC-SENS-1)
  • HOBO RX3000: an analog input module (RXMOD-A1)
  • HOBO U30: an analog input module (VIA)
  • HOBO H22: an analog input module (S-FS-CVIA)

Features

  • Enables users to measure air velocity (in ducts, e.g.), from which CFM can be computed

Specifications

Operating temperature range 0°C to 60°C (32°F to 140°F)
Velocity range 0.15 to 1.0 m/s (30 to 200 fpm)
0.5 to 10 m/s (100 to 2,000 fpm)
1.0 to 20 m/s (200 to 4,000 fpm)
Response time 400ms
Storage temperature -40°C to 105°C (-40°F - 220°F)
Relative humidity (non-condensing) 5-95%
Supply power requirements 4.5-15 VDC, 35mA nominal
Velocity Output 0-5V
Temperature output 0-5V
Housing Construction Polycarbonate (PC), UL94-V0 (head) UL94-HB (housing)
Plenum rated cable 22 AWG
Environmental Protection IP65 electronics, including conformal coated sensing element
Accuracy 0.15 to 1.0 m/s (30 to 200 fpm): ± (1% of reading + 0.05 m/s [10 fpm])
0.5 to 10 m/s (100 to 2,000 fpm): ± (4% of reading + 0.10 m/s [20 fpm])
1.0 to 20 m/s (200 to 4,000 fpm): ± (5% of reading + 0.15 m/s [30 fpm])
Sensor Length 152mm [6.0”]
Max insertion depth 110 mm [4.3”]